IOUT1, 4-20 mA span

usb-iout1-span

Defines the output range of the 4-20 mA signal of IOUT1. The span should cover the expected range of the level or distance, respectively.

EXAMPLE  

Minimum level: 0 cm

Maximum expected level: 400 cm

This gives an offset of 0 cm and a level span of 400 cm. To interpret the output more easily select a span value of 480 cm; thus, a current of 1 mA corresponds to a level of 30 cm.

Value range

Default

Units

-9ˈ999ˈ999…99ˈ999ˈ999

10ˈ000 (default)

Unit of level